Building servicesComfort

Why Is One Cabin Colder Than Another? Uneven Office Temperatures Explained

By Gurpreet Singh, Co-Founder9 min read

Quick answer

When one cabin is colder than another, the AC is usually distributing air unevenly rather than failing. The common causes are rooms sharing one zone and one thermostat, a thermostat placed in the wrong room, diffusers and dampers that were never balanced (or were left as they were after partitions moved), different sun on the glass, and indoor units sized wrongly for the room. Log temperatures for a week and clear blocked grilles first; if the pattern stays, ask an HVAC contractor to measure and rebalance the airflow.

Glass-fronted private cabin beside an open-plan workstation bay, under a white false ceiling with linear air-conditioning diffusers, with roller blinds on sunlit windows
Concept render: a cabin and open bay sharing one ceiling. Illustration, not a completed project.

The MD’s cabin needs a shawl, the finance cabin next door is warm by lunch, and both are on the same AC. This is one of the most common comfort complaints in Indian offices, and it is rarely solved by turning the thermostat down. This guide is for admin and facilities heads, CFOs and founders: why neighbouring cabins end up at different temperatures, what your own team can check safely, and when to bring in an HVAC contractor for air balancing.

Why is one cabin colder than another?

An office AC system is a network: cool air leaves a unit, travels through ducts, comes out of diffusers in each room and returns to the unit through grilles or the ceiling void. Every room gets the share of air that the ducts, dampers and grilles allow. If that share does not match the room’s heat load, one room overcools while another stays warm, even though the system as a whole is working. The table sorts the usual causes.

CauseWhat you noticeWho usually fixes it
Several rooms on one zone and one thermostatThe room with the thermostat is comfortable; the others are too cold or too warmHVAC contractor (rezoning or extra controls)
Thermostat in the wrong placeReadings on the controller do not match how the room feelsFacility team can check; contractor relocates the sensor
Airflow never balanced, or dampers movedThe cabin nearest the unit is cold; the far cabin is warmHVAC contractor (air balancing)
Different sun on the glassOne cabin is fine in the morning and hot in the afternoonFacility team (blinds), then contractor if load is too high
Indoor unit too big or too small for the roomCabin swings between cold and clammy, or never cools on hot daysHVAC contractor
Blocked diffusers or no return pathWeak airflow, stuffy air, the door whistles or slamsFacility team first

Two or three of these often act together. A west-facing cabin that shares a zone with an east-facing one, with a thermostat in the corridor, will be uncomfortable for most of the day whatever the setpoint.

How does one thermostat end up controlling several rooms?

A thermostat can only respond to the temperature where it sits. When one air handler, fan coil unit or ducted indoor unit serves three cabins, the unit runs until its sensor is satisfied. The cabin with the sensor is comfortable. A cabin with more people, more equipment or more sun stays warm, and a lightly used cabin keeps receiving cold air it does not need.

This happens in three common ways:

  • Cabins were added after the AC was designed. An open area became two or three rooms, but the ducted unit above them stayed as one zone.
  • The thermostat was left where it was. It now sits in a corridor, behind a cupboard, near a printer, under a supply diffuser or on a sunlit wall, so it reads a temperature nobody actually sits in.
  • Rooms with very different use share a zone. A meeting room that fills up for two hours and a cabin used by one person have very different loads, so one setting cannot suit both.

The lasting fix is to give rooms with different loads their own control: a separate indoor unit or fan coil unit, or a variable air volume (VAV) box with its own sensor where the building’s system supports it. Our office HVAC design guide explains zoning at the design stage, and VRF vs chilled water covers how each route handles separately controlled rooms.

Were the diffusers and dampers ever balanced?

Air takes the easiest path. Without adjustment, rooms close to the unit or on a short duct run get more air than rooms at the end of a long run. That is why ducted systems have volume control dampers in the branch ducts and adjustable diffusers: after installation, a technician measures the airflow at each outlet and sets the dampers so that each room receives the air it was designed for. This is called air balancing, or testing, adjusting and balancing.

Balancing goes wrong in predictable ways:

  • It was skipped at handover because the project ran late, so the system was never set to the design figures.
  • Partitions moved later. A wall now cuts under a diffuser, or a cabin was resized, but nobody re-measured the air.
  • Dampers were adjusted by hand during a complaint, often fully closed in one room, which pushes extra air into the neighbouring cabins.
  • Diffusers point at people. Air blowing straight onto a desk feels colder than the room temperature suggests, so the occupant complains of cold even when the room reading is normal.

Air also has to get back to the unit. A closed cabin with supply air but no return grille, transfer grille or door undercut builds up pressure: the door may whistle or be hard to close, airflow into the room drops, and the room feels stuffy as well as uncomfortable. If rooms feel heavy even when the temperature is right, the cause is usually fresh air: see why an office feels stuffy.

Small glass-fronted cabin with frosted graphic film, an L-shaped desk, wrapped chairs and cartons awaiting unpacking, next to a printer bay with overhead storage
Work in progress on an Officea fit-out.

Does sun on the glass explain the difference?

Often, yes. Two cabins of the same size can have very different heat loads if one faces west and the other faces into the core. A west-facing cabin can be comfortable at 10 am and warm by 3 pm; an east-facing cabin follows the opposite pattern. If both share one zone, the thermostat cannot satisfy both at once.

A simple test is to log the temperature in both cabins at the same three times a day. If the gap opens and closes with the sun, glass is a large part of the problem. Start with what costs least: blinds that are actually lowered at the hot time of day, and desks moved so nobody sits in direct sun. Solar film may help, but many buildings control what can be applied to the facade glass, so check with the landlord first. If the sunny cabin is still warm, the room needs more supply air or its own control, which is a design question for an HVAC engineer.

Is the indoor unit the right size for the room?

In offices with VRF or split systems, each cabin often has its own indoor unit. That gives individual control, but only if the unit suits the room. An indoor unit that is too large for a small cabin cools the air quickly and switches off before it has removed much moisture, so the room swings between cold and clammy. A unit that is too small cannot keep up on hot afternoons or when the cabin is full.

Two other patterns are common in VRF offices. One indoor unit is sometimes ducted to serve two adjoining cabins, which brings back the single-thermostat problem. And when many indoor units call for cooling at peak hours, units at the end of long refrigerant runs can perform less well than those close to the outdoor unit. Sizing should be checked against today’s layout, occupancy and glass, not the original drawings alone.

What can the facility team check safely?

Your own team can rule out the simple causes before anyone opens the ceiling. Keep to checks that need no tools, ladders into the ceiling void or access to electrical panels and refrigerant lines.

  1. Log temperatures for a week. Use a simple thermometer at desk height in each affected cabin, morning, early afternoon and late afternoon. Note occupancy, door open or closed, and whether blinds were down.
  2. Check thermostat setpoints and modes. Look for cabins set very low “to cool faster”, controllers set to different modes or fan speeds, and timers that switch units off early.
  3. Find the thermostat or sensor. Note whether it sits in the room it controls, and whether it is near a diffuser, a window, a printer or a heat-producing appliance.
  4. Look for blocked diffusers and returns. Files, cupboards, partitions, ceiling-height storage or newly added light fittings can block supply or return grilles.
  5. Check the return path. With the door closed, does the cabin have a return grille, transfer grille or a gap under the door? Does the door whistle or resist closing?
  6. Use the blinds. Lower them on the sunny side for a few days and see whether the logged temperatures change.
  7. Review the service log. Dirty filters on one indoor unit reduce airflow to that room. Check when filters were last cleaned under the maintenance contract.

Do not adjust dampers in the ceiling, change controller settings locked by the building, or open AC equipment yourselves. In buildings on a central plant, the landlord’s facility team controls much of the system, so raise the issue with them as well.

When should you call an HVAC contractor?

Call an HVAC contractor when the temperature log shows a steady pattern that the simple checks have not fixed, when cabins have been added or resized since the AC was installed, or when people are using heaters or shawls in one room while the next room complains of heat.

A proper air balancing visit usually involves measuring airflow at each diffuser with a flow hood or anemometer, comparing it with the design figures, adjusting dampers and diffusers, checking return paths, and recording the results. Ask for a written balancing report showing measured and design airflow for each outlet, and for a note of anything balancing alone cannot fix.

FixWhen it suitsDisruption
Rebalance dampers and diffusersThe ducts and units are right, but air is going to the wrong roomsLow: ceiling access in a few places, often after hours
Move or add thermostats or sensorsThe sensor reads a space nobody sits inLow
Add return or transfer grilles, door undercutsClosed cabins are starved of air or stuffyLow to medium: small joinery and ceiling work
Relocate or change diffusersAir blows onto desks, or a partition sits under a diffuserMedium: ceiling work in the affected rooms
Rezone with separate units, fan coils or VAV boxesRooms with very different loads share one controlHigher: best planned with other work

Larger changes are best combined with any other work planned for the office, so the false ceiling is opened once. If the fit-out is recent and the problem comes from the installation, such as balancing that was never done, check whether it falls within the contractor’s defect liability period.

This is general guidance. HVAC systems differ from building to building: confirm any change with a qualified HVAC engineer, your building’s facility team and the landlord’s rules before work starts.

If the whole floor is struggling rather than one cabin, start with our guide on office AC not cooling or uneven temperatures. For other everyday office issues, browse office problems and solutions. Officea designs and builds offices, including the air conditioning, under one contract from studios in Delhi (Nehru Place), Gurgaon (DLF Grand Mall), Noida (Sector 3) and Bangalore (Residency Road).

Frequently asked questions

Why is one cabin colder than another on the same AC?

Usually because the cabins share one zone and one thermostat, the airflow to each room was never balanced, the thermostat sits in the wrong place, or the cabins get different sun. The system can be working normally while sending more air to one room than it needs.

Should we just lower the thermostat in the warm cabin?

Rarely. If the warm cabin shares a zone with a cold one, lowering the setpoint makes the cold cabin colder. Check zoning, sensor position, blocked grilles and blinds first, then have the airflow measured.

What is air balancing in an office?

Air balancing means measuring the airflow at each diffuser and adjusting dampers and diffusers so every room receives the air it was designed for. It should be done at handover and repeated when partitions or cabins change.

Can our facility team adjust the dampers themselves?

It is better not to. Closing a damper in one cabin pushes extra air into the next one and can upset the whole system. Let an HVAC contractor measure and adjust the airflow and give you a written balancing report.

Does every cabin need its own AC unit?

Not always. Rooms with similar use and orientation can share a zone. Rooms with very different loads, such as a sunny cabin, an internal cabin and a busy meeting room, are easier to keep comfortable with their own control.

Planning an office project?

Officea Design & Build plans, designs and builds corporate offices across India under one contract. See our work or the full list of design and build services, or tell us your city, approximate area and target move-in date below and we'll prepare a costed proposal.

Estimate your fit-out cost

Officea's own 2026 rates by tier. Not a quote — send us your details below for an exact number.

Office fit-out cost per sq ft, 2026 rate card (GST extra). Last updated 11 October 2026.
TierDelhi, Gurgaon, Noida, ChandigarhBangalore, Mumbai, Pune, Hyderabad, Chennai, Goa
Basic₹1,800₹2,000
Medium₹2,200₹2,400
Good₹2,600₹2,900
High end₹4,500₹5,000

Bangalore, Mumbai, Pune, Hyderabad, Chennai and Goa run about 10% above Delhi NCR, rounded to the nearest ₹100. Rates cover civil, MEP, flooring, ceiling and standard finishes. Furniture is included in every Officea quote. See every city and tier side by side in the India office fit-out cost index. Plan workstations, cabins and meeting rooms in the office layout planner. See the city pages for Pune, Hyderabad, Chennai, Chandigarh and Goa.

Fit-out tier
₹1,10,00,000
≈ $115,789 total · ₹2,200 / sq ft (≈ $23.16)

Officea's own 2026 indicative rates per sq ft, covering civil, MEP, furniture and finishes at the stated tier. For early budgeting only — exact pricing is confirmed in a written proposal.

Want the exact number for your office?

Complimentary download

The same cost benchmarks and planning checklist as a PDF you can keep and share with your team.

2026 Office Fit-Out Planning & Cost Guide

  • 2026 city-by-city cost benchmarks
  • What actually moves your cost per square foot
  • A before-you-sign, during-construction and handover checklist