Quick answer
When one cabin is colder than another, the AC is usually distributing air unevenly rather than failing. The common causes are rooms sharing one zone and one thermostat, a thermostat placed in the wrong room, diffusers and dampers that were never balanced (or were left as they were after partitions moved), different sun on the glass, and indoor units sized wrongly for the room. Log temperatures for a week and clear blocked grilles first; if the pattern stays, ask an HVAC contractor to measure and rebalance the airflow.

The MD’s cabin needs a shawl, the finance cabin next door is warm by lunch, and both are on the same AC. This is one of the most common comfort complaints in Indian offices, and it is rarely solved by turning the thermostat down. This guide is for admin and facilities heads, CFOs and founders: why neighbouring cabins end up at different temperatures, what your own team can check safely, and when to bring in an HVAC contractor for air balancing.
Why is one cabin colder than another?
An office AC system is a network: cool air leaves a unit, travels through ducts, comes out of diffusers in each room and returns to the unit through grilles or the ceiling void. Every room gets the share of air that the ducts, dampers and grilles allow. If that share does not match the room’s heat load, one room overcools while another stays warm, even though the system as a whole is working. The table sorts the usual causes.
| Cause | What you notice | Who usually fixes it |
|---|---|---|
| Several rooms on one zone and one thermostat | The room with the thermostat is comfortable; the others are too cold or too warm | HVAC contractor (rezoning or extra controls) |
| Thermostat in the wrong place | Readings on the controller do not match how the room feels | Facility team can check; contractor relocates the sensor |
| Airflow never balanced, or dampers moved | The cabin nearest the unit is cold; the far cabin is warm | HVAC contractor (air balancing) |
| Different sun on the glass | One cabin is fine in the morning and hot in the afternoon | Facility team (blinds), then contractor if load is too high |
| Indoor unit too big or too small for the room | Cabin swings between cold and clammy, or never cools on hot days | HVAC contractor |
| Blocked diffusers or no return path | Weak airflow, stuffy air, the door whistles or slams | Facility team first |
Two or three of these often act together. A west-facing cabin that shares a zone with an east-facing one, with a thermostat in the corridor, will be uncomfortable for most of the day whatever the setpoint.
How does one thermostat end up controlling several rooms?
A thermostat can only respond to the temperature where it sits. When one air handler, fan coil unit or ducted indoor unit serves three cabins, the unit runs until its sensor is satisfied. The cabin with the sensor is comfortable. A cabin with more people, more equipment or more sun stays warm, and a lightly used cabin keeps receiving cold air it does not need.
This happens in three common ways:
- Cabins were added after the AC was designed. An open area became two or three rooms, but the ducted unit above them stayed as one zone.
- The thermostat was left where it was. It now sits in a corridor, behind a cupboard, near a printer, under a supply diffuser or on a sunlit wall, so it reads a temperature nobody actually sits in.
- Rooms with very different use share a zone. A meeting room that fills up for two hours and a cabin used by one person have very different loads, so one setting cannot suit both.
The lasting fix is to give rooms with different loads their own control: a separate indoor unit or fan coil unit, or a variable air volume (VAV) box with its own sensor where the building’s system supports it. Our office HVAC design guide explains zoning at the design stage, and VRF vs chilled water covers how each route handles separately controlled rooms.
Were the diffusers and dampers ever balanced?
Air takes the easiest path. Without adjustment, rooms close to the unit or on a short duct run get more air than rooms at the end of a long run. That is why ducted systems have volume control dampers in the branch ducts and adjustable diffusers: after installation, a technician measures the airflow at each outlet and sets the dampers so that each room receives the air it was designed for. This is called air balancing, or testing, adjusting and balancing.
Balancing goes wrong in predictable ways:
- It was skipped at handover because the project ran late, so the system was never set to the design figures.
- Partitions moved later. A wall now cuts under a diffuser, or a cabin was resized, but nobody re-measured the air.
- Dampers were adjusted by hand during a complaint, often fully closed in one room, which pushes extra air into the neighbouring cabins.
- Diffusers point at people. Air blowing straight onto a desk feels colder than the room temperature suggests, so the occupant complains of cold even when the room reading is normal.
Air also has to get back to the unit. A closed cabin with supply air but no return grille, transfer grille or door undercut builds up pressure: the door may whistle or be hard to close, airflow into the room drops, and the room feels stuffy as well as uncomfortable. If rooms feel heavy even when the temperature is right, the cause is usually fresh air: see why an office feels stuffy.

Does sun on the glass explain the difference?
Often, yes. Two cabins of the same size can have very different heat loads if one faces west and the other faces into the core. A west-facing cabin can be comfortable at 10 am and warm by 3 pm; an east-facing cabin follows the opposite pattern. If both share one zone, the thermostat cannot satisfy both at once.
A simple test is to log the temperature in both cabins at the same three times a day. If the gap opens and closes with the sun, glass is a large part of the problem. Start with what costs least: blinds that are actually lowered at the hot time of day, and desks moved so nobody sits in direct sun. Solar film may help, but many buildings control what can be applied to the facade glass, so check with the landlord first. If the sunny cabin is still warm, the room needs more supply air or its own control, which is a design question for an HVAC engineer.
Is the indoor unit the right size for the room?
In offices with VRF or split systems, each cabin often has its own indoor unit. That gives individual control, but only if the unit suits the room. An indoor unit that is too large for a small cabin cools the air quickly and switches off before it has removed much moisture, so the room swings between cold and clammy. A unit that is too small cannot keep up on hot afternoons or when the cabin is full.
Two other patterns are common in VRF offices. One indoor unit is sometimes ducted to serve two adjoining cabins, which brings back the single-thermostat problem. And when many indoor units call for cooling at peak hours, units at the end of long refrigerant runs can perform less well than those close to the outdoor unit. Sizing should be checked against today’s layout, occupancy and glass, not the original drawings alone.
What can the facility team check safely?
Your own team can rule out the simple causes before anyone opens the ceiling. Keep to checks that need no tools, ladders into the ceiling void or access to electrical panels and refrigerant lines.
- Log temperatures for a week. Use a simple thermometer at desk height in each affected cabin, morning, early afternoon and late afternoon. Note occupancy, door open or closed, and whether blinds were down.
- Check thermostat setpoints and modes. Look for cabins set very low “to cool faster”, controllers set to different modes or fan speeds, and timers that switch units off early.
- Find the thermostat or sensor. Note whether it sits in the room it controls, and whether it is near a diffuser, a window, a printer or a heat-producing appliance.
- Look for blocked diffusers and returns. Files, cupboards, partitions, ceiling-height storage or newly added light fittings can block supply or return grilles.
- Check the return path. With the door closed, does the cabin have a return grille, transfer grille or a gap under the door? Does the door whistle or resist closing?
- Use the blinds. Lower them on the sunny side for a few days and see whether the logged temperatures change.
- Review the service log. Dirty filters on one indoor unit reduce airflow to that room. Check when filters were last cleaned under the maintenance contract.
Do not adjust dampers in the ceiling, change controller settings locked by the building, or open AC equipment yourselves. In buildings on a central plant, the landlord’s facility team controls much of the system, so raise the issue with them as well.
When should you call an HVAC contractor?
Call an HVAC contractor when the temperature log shows a steady pattern that the simple checks have not fixed, when cabins have been added or resized since the AC was installed, or when people are using heaters or shawls in one room while the next room complains of heat.
A proper air balancing visit usually involves measuring airflow at each diffuser with a flow hood or anemometer, comparing it with the design figures, adjusting dampers and diffusers, checking return paths, and recording the results. Ask for a written balancing report showing measured and design airflow for each outlet, and for a note of anything balancing alone cannot fix.
| Fix | When it suits | Disruption |
|---|---|---|
| Rebalance dampers and diffusers | The ducts and units are right, but air is going to the wrong rooms | Low: ceiling access in a few places, often after hours |
| Move or add thermostats or sensors | The sensor reads a space nobody sits in | Low |
| Add return or transfer grilles, door undercuts | Closed cabins are starved of air or stuffy | Low to medium: small joinery and ceiling work |
| Relocate or change diffusers | Air blows onto desks, or a partition sits under a diffuser | Medium: ceiling work in the affected rooms |
| Rezone with separate units, fan coils or VAV boxes | Rooms with very different loads share one control | Higher: best planned with other work |
Larger changes are best combined with any other work planned for the office, so the false ceiling is opened once. If the fit-out is recent and the problem comes from the installation, such as balancing that was never done, check whether it falls within the contractor’s defect liability period.
This is general guidance. HVAC systems differ from building to building: confirm any change with a qualified HVAC engineer, your building’s facility team and the landlord’s rules before work starts.
If the whole floor is struggling rather than one cabin, start with our guide on office AC not cooling or uneven temperatures. For other everyday office issues, browse office problems and solutions. Officea designs and builds offices, including the air conditioning, under one contract from studios in Delhi (Nehru Place), Gurgaon (DLF Grand Mall), Noida (Sector 3) and Bangalore (Residency Road).
Frequently asked questions
Why is one cabin colder than another on the same AC?
Usually because the cabins share one zone and one thermostat, the airflow to each room was never balanced, the thermostat sits in the wrong place, or the cabins get different sun. The system can be working normally while sending more air to one room than it needs.
Should we just lower the thermostat in the warm cabin?
Rarely. If the warm cabin shares a zone with a cold one, lowering the setpoint makes the cold cabin colder. Check zoning, sensor position, blocked grilles and blinds first, then have the airflow measured.
What is air balancing in an office?
Air balancing means measuring the airflow at each diffuser and adjusting dampers and diffusers so every room receives the air it was designed for. It should be done at handover and repeated when partitions or cabins change.
Can our facility team adjust the dampers themselves?
It is better not to. Closing a damper in one cabin pushes extra air into the next one and can upset the whole system. Let an HVAC contractor measure and adjust the airflow and give you a written balancing report.
Does every cabin need its own AC unit?
Not always. Rooms with similar use and orientation can share a zone. Rooms with very different loads, such as a sunny cabin, an internal cabin and a busy meeting room, are easier to keep comfortable with their own control.