Key points
- VRF suits offices with many rooms, uneven hours or zones that often run at part load.
- Ducted splits suit small offices or a few large zones on a tighter budget.
- If the building has central chilled water and your hours match it, tapping in is usually cheaper upfront.
- Size from a heat-load calculation and get outdoor unit locations approved before the layout is frozen.
Is VRF or ducted split AC better for an office?
For offices with many rooms, uneven hours or zones that often run at part load, VRF usually wins, because one variable-speed system serves many indoor units and each room can be controlled separately. For a small office or a few large open zones on a tight budget, ducted splits are simpler and cost less upfront.
VRF vs ducted split compared
| VRF | Ducted split | |
|---|---|---|
| Upfront cost | Higher | Lower |
| Part-load efficiency | Strong: variable-speed compressors follow the load | Depends on the units; you save by switching zones off |
| Zoning and control | Room by room, with central controls | One zone per unit |
| After-hours use | Run only the rooms you need | Run only the units you need |
| Outdoor space | Fewer, larger outdoor units | One outdoor unit per indoor unit |
| Pipes and ducts | Long refrigerant runs that need careful design and leak testing | Short pipe runs, but larger ducts in the ceiling void |
| Servicing | Specialist | Widely available |
| If a unit fails | A fault in an outdoor unit can affect several rooms | Affects one zone |
Which system fits your office?
| If this is you | Better choice | Why |
|---|---|---|
| Many cabins and meeting rooms, uneven use | VRF | Each room controlled separately, efficient at part load |
| Small office or a few large open zones, tight budget | Ducted split | Lower upfront cost, simple servicing |
| Building has chilled water and your hours match | Building chilled water | Usually cheapest upfront; check after-hours charges |
| 24x7 teams or irregular hours | VRF | Full control without running the building plant |
| Little outdoor ledge or terrace space | VRF | Fewer outdoor units |
When should you use the building’s chilled water instead?
When the building has a central chilled water plant and your working hours match the building’s. Tapping into it with your own air handling units is usually cheaper upfront; VRF makes more sense for 24x7 or irregular hours, or where there is no central plant.
Warm shell floors in Grade A buildings often come with the building’s air conditioning, while bare shell floors leave the choice to you; see bare shell vs warm shell. Check the after-hours charges for building chilled water before deciding, because they decide the running cost for teams that work late. The full comparison is in VRF vs chilled water HVAC and the office HVAC design guide.
What does the landlord need to approve for VRF or split AC?
Where the outdoor units go, the routes for refrigerant pipes and condensate drains, any openings in walls or slabs, the electrical load, and how the units look and sound on the terrace or facade. Get this approved before the layout is frozen.
Outdoor space is often the deciding constraint: ducted splits need one outdoor unit per indoor unit, which takes more ledge or terrace space than a VRF system. The approval steps are in the Grade A landlord fit-out approval checklist.
How should office air conditioning be sized?
From a heat-load calculation for your actual layout, not a rule of thumb, because density, glazing, orientation and the number of meeting rooms all change the load.
Meeting rooms and training rooms need much more cooling per sq ft than open desks, and server rooms need dedicated cooling that runs around the clock. Indicative ranges and fresh air rules are in the office HVAC design guide. When an existing office runs warm or unevenly cooled, see why an office AC is not cooling and how to fix it.
What should an office AC quote include?
The heat-load calculation, equipment make and model with capacity and efficiency, an indoor unit schedule by room, piping, ducting, drains and insulation, controls, fresh air, testing and commissioning, and the warranty terms.
Two quotes that leave out different items cannot be compared. Ask both bidders to price the same heat-load and unit schedule, and to state what is excluded, such as civil openings, electrical cabling to the units or the landlord’s connection charges.
See every Officea comparison, each with a short answer, on the office fit-out comparisons page.